Schneider MCB iK60N A9K27220 2 Poles 20 Ampere 6kA - A9K27220
Rp323.600 Rp161.800 50% off! Sale!
Schneider MCB iK60N A9K27220 2 Poles 20 Ampere 6kA. This Acti9 iK60N product is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles and 20A In rated current and C tripping curve. The rated short circuit breaking capacity goes up to 6000A at 230VAC conforming to EN/IEC 60898-1 standard and at conforming to standard. This product is compliant with EN/IEC 60898-1 standard. This miniature circuit breaker protects circuit against short circuit and overload current.
It has a double clip for dismounting with comb busbar in place. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 4kV. The operating frequency is 50Hz or 60Hz. It can be mounted on DIN rail for modular installation. Its width is 4 pitches of 9mm. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 78.5mm. The weight is 200g. It has an IP20 degree of protection. It becomes IP40 once in modular enclosure according to IEC/EN 60529 standard. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C.
Schneider MCB iK60N A9K27220 Main Specification
- Thermal-magnetic trip unit technology
- 2 poles
- 20 Ampere at 30 °C [In] rated current
- 6000 A breaking capacity at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
- Suitability for isolation conforming to EN/IEC 60898-1
- EN/IEC 60898-1 standards
- AENOR product certifications
- Network frequency at 50/60 Hz
- Magnetic tripping limit at 5…10 x In
- 6000 A 100 % rated service breaking capacity conforming to EN/IEC 60898-1 – 230 V AC 50/60 Hz
- 3 limitation class conforming to EN/IEC 60898-1
- 440 V AC 50/60 Hz rated insulation voltage conforming to EN/IEC 60898-1
- 4 kV of rated impulse withstand voltage conforming to EN/IEC 60898-1
- Toggle control type
- ON/OFF indication for local signaling
- Clip-on mounting mode
- DIN rail mounting support
- 20000 cycles of mechanical durability
- 10000 cycles of electrical durability
- Padlocking device locking options description
- 14 mm wire stripping length for top or bottom connection
- 2 N.m top or bottom tightening torque
- Without earth-leakage protection
- IP20 of IP degree of protection conforming to IEC 60529
- 2 pollution degree conforming to EN/IEC 60898-1
- MCB iK60N 2 Poles 20 Ampere III overvoltage category
- Ambient air temperature for operation at -25 to 60 °C
- Ambient air temperature for storage at -40 to 85 °C
Low stock