Schneider LRD07 Thermal Overload Relay 1.6-2.5 A Class 10 - LRD07
Rp530.600 Rp281.300 47% off! Sale!
Schneider LRD07 Thermal Overload Relay 1.6 – 2.5 A Class 10
Schneider LRD07 Differential Thermal Overload Relay Main Specifictaion
- Range:
- Product name:
- LRD device short name
- Differential thermal overload relay product type
- Motor protection relay application
- Product compatibility:
- LC1D18
- LC1D38
- LC1D32
- LC1D25
- LC1D12
- LC1D09
- DC & AC network type
- Class 10 A thermal overload class conforming to IEC 60947-4
- 1.6 – 2.5 Ampere thermal protection adjustment range
- Rated insulation voltage Power circuit:
- 690 V conforming to BS 4941
- 690 V conforming to IEC 60947
- 750 V conforming to VDE 0110 group C
- 600 V conforming to CSA C22.2 No 14
Complementary
- Network frequency 0 – 400 Hz
- Mounting support:
- Under contactor
- Plate, with specific accessories
- Rail, with specific accessories
- 1 NO + 1 NC contacts type and composition
- 5 Ampere conventional free air thermal current for control circuit
- Permissible current:
- 3 A at 120 V AC-15 for signalling circuit
- 0.22 A at 125 V DC-13 for signalling circuit
- Rated operational voltage:
- 690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
- Associated fuse rating:
- 4 A gG for signalling circuit
- 4 A BS for signalling circuit
- 6 kV rated impulse withstand voltage conforming to IEC 60947-1
- 2 W power dissipation per pole
- Phase failure sensitivity Tripping current 130 % of Ir on two phase, the last one at 0 conforming to IEC 60947-4-1
- Control type:
- Red push-button: stop
- Blue push-button: reset
- Screw clamp terminals:
- 1 cable 1.5…4 mm²solid
- 2 cables 1.5…4 mm²solid
- 1 cable 0.75…4 mm²flexible without cable end
- 2 cables 0.75…4 mm²flexible without cable end
- 1 cable 0.34…2.5 mm²flexible with cable end
- 2 cables 0.34…1.5 mm²flexible with cable end
- Tightening torque:
- Control circuit: 1.7 N.m – on screw clamp terminals
- Power circuit: 1.7 N.m – on screw clamp terminals
Environment
- Climatic withstand conforming to IACS E10
- Â Standards:
- VDE 0660
- IEC 60947
- NF C 63-650
- BS 4941
- Product certifications:
- Protective treatment:
- TC conforming to IEC 60068
- TC conforming to DIN 50016
- IP20 conforming to IEC 60529
- Ambient air temperature:
- -20…55 °C without derating conforming to IEC 60947
- -30…60 °C with derating conforming to IEC 60947
- -40…85 °C ambient air temperature for storage
- 2000 m without derating operating altitude
- 850 °C fire resistance conforming to IEC 60695-2-1
- Flame retardance:
- V1 conforming to UL 94
- Requirement 2 conforming to NF F 16-101
- Requirement 2 conforming to NF F 16-102
- Mechanical robustness:
- Shocks NO contact: 10 Gn for 11 ms conforming to IEC 60068-2-27
- Shocks NC contact: 10 Gn for 11 ms conforming to IEC 60068-2-27
- Vibrations NO contact: 2 Gn, 5…300 Hz conforming to IEC 60068-2-6
- Vibrations NC contact: 2 Gn, 5…300 Hz conforming to IEC 60068-2-6
Relay Thermal Beban Lebih untuk kontaktor TeSys (Koneksi Standar) 09 – 38 | 16A – 25A