Schneider EOCR LT4706M7S Auto Reset 0.5A – 6A 200-240 VAC - LT4706M7S
Rp1.787.200 Rp965.100 46% off! Sale!
Schneider EOCR LT4706M7S Auto Reset 0.5A – 6A Electronic Over Current Relay 200-240 VAC
Schneider EOCR LT4706M7S Auto Reset Electronic Over Current Relay Main Specification
- TeSys LT product name
- Electronic over current relay product or component type
- LT47 device short name
- Protection device application
- Relay application:
- Overload Imax > Isetting
- Locked rotor, mechanical jamming I > 3 x Isetting
- Sensitivity to phase failure
- Rated supply voltage:
- 0.5A – 6A thermal protection adjustment range
- Rated insulation voltage Power circuit at 600 V AC conforming to:
Complementary
- 50…60 Hz network frequency
- Rail mounting support
- 0.5A – 5 A tripping threshold
- Electromagnetic compatibility:
- Resistance to electrostatic discharge: 8 kV in open air conforming to IEC 61000-4-2
- Resistance to electrostatic discharge: 6 kV in direct mode conforming to IEC 61000-4-2
- Conducted emission: class A conforming to EN 55011
- Immunity to electromagnetic interference: 10 V/m conforming to IEC 61000-4-3
- Immunity to fast transients: 2 kV conforming to IEC 61000-4-4
- Surge withstand: 6 kV conforming to IEC 61000-4-5
- Conducted HF disturbances: 10 V conforming to IEC 61000-4-6
- 1 NO + 1 NC auxiliary contact composition
- 3 A for signalling circuit conventional free air thermal current
- Associated fuse rating:
- 3 A gG for signalling circuit
- 3 A BS for signalling circuit
- 6 kV rated impulse withstand voltage
- Time range:
- 1…120 s – control type R-time
- 0.3…30 s – control type O-time
- Local signalling:
- 1 LED (green)
- 1 LED (red)
- Automatic: reset control type
- Connections – terminals:
- Signalling circuit, screw clamp terminals 1:
- 1…2.5 mm² – cable stiffness: flexible with cable end
- 1…2.5 mm² – cable stiffness: flexible without cable end
- Signalling circuit, screw clamp terminals 2:
- 1…2.5 mm² – cable stiffness: flexible with cable end
- 1…2.5 mm² – cable stiffness: flexible without cable end
- Signalling circuit: 1.7 N.m M3.5 tightening torque
Environment
- IEC 60255-6 & IEC 60947 standards
- UL & CSA product certifications
- TH protective treatment conforming to IEC 60068
- IP degree of protection:
- IP20 conforming to IEC 60529
- IP20 conforming to VDE 0106
- -25…60 °C ambient air temperature for operation without derating conforming to IEC 60947-4-1
- -30…80 °C ambient air temperature for storage
- 2000 m operating altitude
- Mechanical robustness:
- Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
- Vibrations: 4 gn conforming to IEC 60068-2-6
- Dielectric strength 2 kV at 50 Hz conforming to IEC 60255-5