MCCB NSXm100E 4P 125A 16kA LV426118 Schneider - C12E6TM125L
Rp3.617.500 Sale!
MCCB NSXm100E 4P 125A 16kA with Everlink TMD Connectors LV426118 Schneider
MCCB NSXm100E 4P 125A Main
- 125A rated current at 40 °C
- 690 V AC 50/60 Hz  rated operational voltage
- AC network type & 50/60 Hz network frequency
- Suitability for isolation conforming to EN/IEC 60947-2
- MCCB NSXm100E 4P 125A rated ultimate short-circuit breaking capacity:
- 25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
- 16 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
- 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
- 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
- 16 kA performance level at 415 V AC
- TM-D trip unit name
- Thermal-magnetic trip unit technology
- Toggle control type
- Circuit breaker mounting mode:
Complementary
- 800 V AC 50/60 Hz rated insulation voltage
- 8 kV rated impulse withstand voltage
- Rated service short-circuit breaking capacity:
- 25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
- 16 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
- 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
- 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
- 20000 cycles of mechanical durability
- Electrical durability:
- 10000 cycles at 440 V In
- 20000 cycles at 440 V In/2
- 5000 cycles at 690 V In
- 10000 cycles at 690 V In/2
- Plate & DIN rail mounting support
- Connection terminals:
- 1 Everlink lug wire size 2.5…95 mm², rigid or stranded aluminium/copper
- 1 Everlink lug wire size 2.5…70 mm², flexible copper
- Connection pitch:
- 35 mm with spreaders
- 27 mm without spreaders
- 9 modules 9 mm pitches
- Protection type:
- L : for overload protection (thermal)
- I : for short-circuit protection (magnetic)
- Adjustable Long-time pick-up adjustment type Ir (thermal protection)
- 0.7…1 x In for long-time protection pick-up adjustment range
- Fixed Long-time protection delay adjustment type tr
- 500 A magnetic protection pick-up range
- Without earth-leakage protection
- 1 slot for all electrical auxiliaries bellow:
- auxiliary switch OF
- alarm switch SD
- voltage release MN or MX
Environment
- EN/IEC 60947 standards
- Product certifications:
- 3 pollution degree conforming to IEC 60664-1
- IP40 protection conforming to IEC 60529
- IK07 protection conforming to IEC 62262
- Ambient air temperature for operation at -25 to 70 °C
- Ambient air temperature for storage at -50 to 85 °C
- 0 to 95 % relative humidity
- Operating altitude:
- 0 to 2000 m without derating
- 2000 to 5000 m with derating
MCCB NSXm100 E 4P 125A 16kA with Everlink TM Connectors