MCCB NSX100H 4P 100A 70kA C10H6TM100 Schneider - C10H6TM100
Rp4.313.500 Sale!
MCCB NSX100H 4P 100A 70kA C10H6TM100 Schneider
MCCB NSX100H 4P 100A Main Specification
- Rated operational voltage at 690 V AC 50/60 Hz
- AC network type
- Suitability for isolation conforming to EN/IEC 60947-2
- MCCB NSX100H 4P 100A rated ultimate short-circuit breaking capacity:
- 10 kA at 600 V AC 50/60 Hz conforming to UL 508
- 85 kA at 240 V AC 50/60 Hz conforming to UL 508
- 65 kA at 480 V AC 50/60 Hz conforming to UL 508
- 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
- 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
- 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
- 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
- 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
- 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
- Performance level 70 kA 415 V AC
- TM-D trip unit
- Thermal-magnetic trip unit technology
- LI trip unit protection functions
- Toggle control type
- Fixed Circuit breaker mounting mode
Complementary
- 800 V AC 50/60 Hz rated insulation voltage
- 8 kV rated impulse withstand voltage
- Rated service short-circuit breaking capacity:
- 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
- 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
- 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
- 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
- 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
- 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
- 50000 cycles mechanical durability
- Electrical durability:
- 10000 cycles at 690 V In
- 20000 cycles at 690 V In/2
- 30000 cycles at 440 V In
- 50000 cycles at 440 V In/2
- 8.8 W power losses
- Backplate mounting support
- Front upside connection
- Front downside connection
- 35 mm connection pitch
- Protection type:
- L : for overload protection (thermal)
- I : for short-circuit protection (magnetic)
- Adjustable Long-time pick-up adjustment type Ir (thermal protection)
- 0.7…1 x In long-time protection pick-up adjustment range
- Fixed Long-time protection delay adjustment type tr
- Long-time protection delay adjustment range:
- 120 – 400 s at 1.5 x In
- 15 s at 6 x Ir
- Fixed Short-time protection pick-up adjustment type Isd
- 800 A Short-time protection pick-up adjustment range
- Fixed Short-time protection delay adjustment type tsd
- Without earth-leakage protection
- No Neutral protection settings
- 5 slots for electrical auxiliaries
Environment
- EN/IEC 60947 standards
- Product certifications:
- Class II overvoltage category
- Class II electrical shock protection class
- IP40 from IP degree of protection conforming to IEC 60529
- IK07 from IK degree of protection conforming to IEC 62262
- Ambient air temperature for operation at -25 to 70 °C
- Ambient air temperature for storage at -50 to 85 °C
- 0 – 95 % relative humidity
- Operating altitude:
- 0 to 2000 m without derating
- 2000 m to 5000 m with derating
MCCB NSX100 H 4P 100A 70kA
Out of stock
Reviews
There are no reviews yet.